SV01B

Purpose:

  • Measuring vibration velocity of an object and producing a warning signal of exceeding the preset vibration level in the form of closed or open relay contacts.

Features:
  • Two-wire connection line.
  • No additional power supply needed.
  • Signal transmission at a distance of up to 100 metres.
  • Custom-programmed main parameters.
  • Conformity to GOST ISO 10816.
  • Explosion-proof version 1ExibIICT5 .
  • Parameter
    Units of Measure
    SV01B
  • Operating frequency range at: -1 dB
     Hz
    2...1 000
  • Preset operating threshold value (RMS)/minimum operating threshold step
     mm/s*1
    1 ... 99.9/0.1; 100 ... 200/1
  • Operation thresholding error
    %
     ±3
  • Additional error in the temperature range from –40°С to +85°С
    %
     ±5
  • Run mode setting time after power-on
    s
    <10
  • Actuation signal criteria
    informative signal is continuously exceeding the threshold value during 0-9 s*1
  • Actuation mode
    blocking / self-recovery*1
  • Self-recovery conditions
     vibration decrease by 6% of the operating threshold
  • Vibration control delay (after setting an operating or self-recovery mode)
    s
     0 or 20*1
  • Relay contact parameters:
    - switching current;
    - switching voltage;
    - voltage drop:
     at 15 mA;
     at 500 mA;
    in position:

    mA;
    V;

    V;
    V;

    15 ... 500;
    15 ... 30;

    <4;
    <7;
    closed / open*1
  • Current consumption in an open position
    mA
     <1.5
  • Operating temperature range
    °С
    –40 ... +85
  • Type of connector
    AR07
  • Housing material
     stainless steel
  • Weight (without cable)
    g
    120
  • Supplied accessories
    cable АК31С1А3, stud АН0106
External view of SV01B
Electrical circuit of SV01B
Wiring example of vibration switch SV01B

Optional accessories:

  • calibrator AT02;
  • programming panel SVProg;
  • stud AH1006.

 
*1 – To be determined by customer or programmed via SVProg.